Supporting Type Current Transformer
IGWK D28
The IGWK..D28 is used for measurement and protection in applications. This model is specially designed for an extended creepage distance.
5 - 2500A
1A or 5A, other options available on request
As required. For example 0,2S, 5P10

"Our customers expect us to be able to offer them a solution for every challenge. For which challenge are you looking for a solution?"
Jerry van Zundert, Sales Manager
+31 (0) 521 533 333
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-5°C .. +40°C, other temperatures on request
5% .. 95%, non condensing
Application conditions
IEC 61869-2/IEEE C57.13, etc.
100 x In/1s, max. 50kA/1s
2,5 x Ith, max. 125kA/1s
24/50/125kV
50/60Hz
M12 (40Nm)
Screw terminals M5 (max. 2,5Nm)
As required. For example 2,5, 10 or 30VA