IGWK D28

Supporting Type Current Transformer

The IGWK..D28 is used for measurement and protection in applications. This model is specially designed for an extended creepage distance.

Primary current:5 - 2500A
Secondary current:1A or 5A, other options available on request
Accuracy class:As required. For example 0,2S, 5P10
M12 (40Nm)IGWK D28

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Relative humidity5% .. 95%, non condensing

Application conditions

StandardIEC 61869-2/IEEE C57.13, etc.
Rated short-time thermal current (Ith)100 x In/1s, max. 50kA/1s
RatedDynamicCurrentIdyn2,5 x Ith, max. 125kA/1s
Rated insulation level24/50/125kV
Rated frequency50/60Hz
Rated outputAs required. For example 2,5, 10 or 30VA
Primary connectionM12 (40Nm)
Secondary terminalScrew terminals M5 (max. 2,5Nm)
IGWK D28

Downloads for IGWK D28

1Downloads available
Wim van Turennout

Talk to sales

“We are the international manufacturer of measuring, revenue metering and protection transformers for energy generation, energy transport and distribution, energy accounting and energy management. Please contact me for the best solution for you.”

Wim van Turennout, Key Account Manager
IGWK D28

IGWK D28