M10 (20Nm)

Generator Voltage Transformer
UGER D25
The UGER D25 is used for measurement and protection in applications with vibration requirements like power generators. The single pole indoor voltage transformer can be used up to 17,5kV.
2/√3kV -15/√3kV
100/√3V or 110/√3V, other options available on request
As required. For example 10, 15 or 30VA

Our customers expect us to be able to offer them a solution for every challenge. For which challenge are you looking for a solution?
Aafje Heinhuis, Inside Sales
+31 (0)521 533 333
Order specifications
For the customized design of your ELEQ voltage transformer the following information is required:
Mandatory
•Rated primary voltage
•Rated secondary voltage
•Rated output
•Accuracy class
•Frequency
Optional
•Transformer requirement with separated windings
•Other relevant requirements
Mandatory
•Rated primary voltage
•Rated secondary voltage
•Rated output
•Accuracy class
•Frequency
Optional
•Transformer requirement with separated windings
•Other relevant requirements
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-25°C .. +80°C, other temperatures on request
5% .. 95%, non condensing
Max. 1000m above NN; at >1000m data required
IP20
Application conditions
IEC 61869-3 / IEEE C57.13, etc.
500VA measuring winding 100VA residual winding
1,9 x Un for 8 h, 1,2 x Un continuous
17,5/38/75kV
50/60Hz
E
M10 (20Nm)
Screw terminals M5 (max. 2,5Nm)
As required. For example 0,2, 3P