UGE D2

Single Pole Voltage Transformer

The UGE D2 is used for measurement and protection in applications, especially in medium-voltage switchgears. The single pole indoor voltage transformer can be used up to 24kV.

Input:2/√3kV - 22/√3kV
Secondary voltage:100/√3V or 110/√3V, other options available on request
Rated output:As required. For example 10, 15 or 30VA
M10 (20Nm)UGE D2

Order specification

Rated outputRatioWinding 1Winding 2RangeArticle number
As required. For example 10, 15 or 30VA5.400:√3 / 110:√3 / 110:330VA cl 0.230VA 3P17,5 kV6U1191
As required. For example 10, 15 or 30VA6.600:√3 / 110:√3 / 110:330VA cl 0.230VA 3P17,5 kV6U1192
As required. For example 10, 15 or 30VA10.000:√3 / 110:√330VA cl 0.2-17,5 kV6U2191
As required. For example 10, 15 or 30VA11.000:√3 / 110:√3 / 110:330VA cl 0.230VA 3P17,5 kV6U2192
As required. For example 10, 15 or 30VA15.400:√3 / 110:√330VA cl 0.2-17,5 kV6U3191
Rated outputRatioWinding 1Winding 2RangeArticle number
As required. For example 10, 15 or 30VA20.000:√3 / 100:√3 / 100:30-20VA cl 0.260VA 3P24 kV6U4011
As required. For example 10, 15 or 30VA22.000:√3 / 100:√3 / 100:30-20VA cl 0.260VA 3P24 kV6U4012
As required. For example 10, 15 or 30VA22.000:√3 / 110:√3 / 110:30-20VA cl 0.260VA 3P24 kV6U4110
As required. For example 10, 15 or 30VA20.000:√3 / 110:√3 / 110:30-20VA cl 0.260VA 3P24 kV6U4112

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Storage and transport temperature-25°C .. +50°C
Relative humidity5% .. 95%, non condensing
AltitudeMax. 1000m above NN; at >1000m data required
Protection degree (secondary terminal)IP20

Application conditions

StandardIEC 61869-3/IEEE C57.13, etc.
RatedThermalLimitingOutputSth500VA measuring winding in total 100VA residual winding
Rated voltage factor1,9 x Un for 8 h, 1,2 x Un continuous
Rated insulation level24/50/125kV
Rated frequency50/60Hz
Class of insulationE
Rated primary voltage2/√3kV - 22/√3kV
Rated secondary voltage100/√3V or 110/√3V, other options available on request
Rated outputAs required. For example 10, 15 or 30VA
Primary connectionM10 (20Nm)
Secondary terminalScrew terminals M5 (max. 2,5Nm)
Accuracy classAs required. For example 0,2, 3P
UGE D2