SVU

Voltage Transformer for Low Voltage 1,2 x Un

Among other things decentralized generation (solar panels, wind turbines) is leading to an increasing number of unusual voltages, such as 690V. To still use the standard meters (400/230V), ELEQ has developed a new line of voltage transformers for low voltage.

Rated primary voltage:Max. 1000V
Rated secondary voltage:Max. 400V
Class:0,2, 0,5, 1, 3
Max. 1000VSVU

Order specification

ModelRated outputAccuracy classRatioArticle number
SVU0-8 VA0,2400/110 V4U4123
SVU0-8 VA0,2690/400 V4U4165
SVU0-8 VA0,2480√3/100√3 V4U4232
SVU0-8 VA0,2600√3/100√3 V4U4252
SVU0-8 VA0,2600√3/400√3 V4U4255
ModelRated outputAccuracy classRatioArticle number
SVU0-8 VA0,2690√3/110√3 V4U4263
SVU0-8 VA0,2690√3/400√3 V4U4265
SVU0-8 VA0,2800√3/100√3 V4U4282
SVU0-8 VA0,2800√3/400√3 V4U4285
SVU5-20 VA0,5On requestOn request

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Operating temperature-25°C .. +55°C
Storage and transport temperature-40°C .. +55°C
Relative humidity5% .. 95%, non condensing
AltitudeMax. 1000m above NN; at >1000m data required
Protection degree IP20

Application conditions

StandardIEC 61869-3
Rated voltage factor1,2 x Un
Rated insulation level0,72/3/-kV or 1,2/6/-kV
Rated frequency50Hz
Class of insulationE
Rated primary voltageMax. 1000V
Burden4, 8, 10, 20, 40, 50, 100VA
Rated secondary voltageMax. 400V
SVU

Downloads for SVU

1Downloads available
Vincent Gorte

Talk to sales

"We never go for the simplest solution, but for the best solution, for you, as a customer. Please contact me for the best solution for you."

Vincent Gorte, Key Account Manager
SVU

SVU