SVA150B50

Cast-resin Current Transformer

The SVA150 is specially designed for application in medium voltage installations as Ring Main Units.

Ratio:200/5A
Class:0,2 FS5
Burden:15VA
Ø 50 mmSVA150B50

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C
Relative humidity5% .. 85%, non condensing
Protection degree IP20

Application conditions

StandardIEC 61869-2
Rated short-time thermal current (Ith)60 x In/1s
Continuous thermal current (Icth)1.2
Rated insulation level0,72/3/-kV
Rated frequency50/60Hz
Class of insulationE
Primary window dimensions (mm)Ø 50 mm
Primary current30-500A
Secondary terminalScrew terminals (max. 2Nm). Wire diameter max. 6mm² solid max 4mm² stranded
On request are other specifications for measuring and protection classes possible. Also multi-core and multi ratio types can be made on request.
SVA150B50