SVA105-100-50

Cast-resin Current Transformer

The SVA105-100-50 is especially designed for application in medium voltage installations around insulated cables.

Ratio:100/5A .. 600/5A and 100/1A .. 600/1A
Class:0,2S, 0,5S, 1, 5P10, 10P10
Burden:1,5-10 VA
Max Ø 50 mmSVA105-100-50

Order specification

BurdenModelRatioClassArticle number
3-5VASVA105-100-50100/1A0,5-14SV501
3-5VASVA105-100-50200/1A0,5-14SV502
3-5VASVA105-100-50300/1A0,5-14SV503
3-5VASVA105-100-50400/1A0,5-14SV504
3-5VASVA105-100-50600/1A0,5-14SV506
2,5VASVA105-100-50100/5A0,2S4SV521
2,5VASVA105-100-50200/5A0,2S4SV522
5VASVA105-100-50100/5A0,5S4SV531
7,5VASVA105-100-50200/5A0,5S4SV532
10VASVA105-100-50300/5A0,5S4SV533
10VASVA105-100-50400/5A0,5S4SV534
BurdenModelRatioClassArticle number
10VASVA105-100-50600/5A0,5S4SV536
4VASVA105-100-50150/1A5P104SV550
4-7VASVA105-100-50100-200/1A5P104SV551
4-7VASVA105-100-50200-400/1A5P104SV552
4-7VASVA105-100-50300-600/1A5P104SV553
4-7VASVA105-100-50400-600/1A5P104SV554
1,5-3VASVA105-100-50100-200/1A0,2S4SV559
1,5-3VASVA105-100-50300-600/1A0,2S4SV560
1,5-3-6VASVA105-100-5050-100-200/1A10P104SV590
1VASVA105-100-50200/5A5P304SV591

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-10°C .. +55°C
Relative humidity5% .. 85%, non condensing
Protection degree IP20

Application conditions

StandardIEC 61869-2
Rated short-time thermal current (Ith)20 kA3s
Continuous thermal current (Icth)100%
Rated insulation level0,72/3/-kV
Rated frequency50/60Hz
Class of insulationE (120°C)
Primary window dimensions (mm)Max Ø 50 mm
Secondary leadsScrew terminals Ø 5mm. Wire diameter max. 6mm² solid max 4mm² stranded
SVA105-100-50