IGW D12

Supporting Type Current Transformer

The IGW D12 is used for measurement and protection in applications. The cast resin insulated indoor supporting-type current transformer can be used up to 24kV.

Primary current:5 .. 1000A
Secondary current:1A or 5A, other options available on request
Accuracy class:As required. For example 0,2S, 5P10
M12 (40Nm)IGW D12

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Relative humidity5% .. 95%, non condensing

Application conditions

StandardIEC 61869-2/IEEE C57.13, etc.
Rated short-time thermal current (Ith)100 x In/1s, max. 50kA/1s
RatedDynamicCurrentIdyn2,5 x Ith, max. 125kA/1s
Rated insulation level24/50/125kV
Rated frequency50/60Hz
Rated outputAs required. For example 2,5, 10 or 30VA
Primary connectionM12 (40Nm)
Secondary terminalScrew terminals M5 (max. 2,5Nm)
IGW D12

Downloads for IGW D12

1Downloads available
Vincent Gorte

Talk to sales

"We never go for the simplest solution, but for the best solution, for you, as a customer. Please contact me for the best solution for you."

Vincent Gorte, Key Account Manager
IGW D12

IGW D12