GST 170 earth fault

Split-Core Current Transformer

The GST 170 are cast-resin insulated current transformers for indoor applications. They are suitable for cables or bus-bars. The GST 170 Earth-fault is dedicated to measure phase displacement of a current. Both fixed core transformers (GSA) and split-core transformers are available (GST/GSK).

Rated primary current:60A
Rated secondary current:1A
Rated output:As required. For example 1,2VA
GST 170 earth fault

Order specification

ModelArticle number
GST 170-B-1106T2060
GST 170-B-1406T2072

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Storage and transport temperature-25°C .. -50°C
Relative humidity5% .. 95%, non condensing
AltitudeMax. 1000m above NN; at >1000m data required
Protection degree (secondary terminal)IP20

Application conditions

StandardIEC 61869-2
Rated short-time thermal current (lth)20 kA / 1 s
RatedDynanimcCurentLdyn2,5 x Ith
Rated insulation level0,72/3/-kV
Rated frequency50/60Hz
Class of insulationE
Rated secondary current1A
Secondary terminalScrew terminals M5 (max. 2,5Nm)
Rated primary current60A
Accuracy class1,2VA - 1Fs10
Rated continuous thermal currentUp to 200%