GSKF 400

Split-Core Current Transformer

GSKF Split-Core Current Transformers: perfect design offering full flexibility and compliance with all regulations.

Primary current:30A ... 10000A
Secondary current:1A or 5A; other options available on request
Accuracy class:As required
GSKF 400

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationOutdoor use
Ambient air temperature-25°C .. +40°C; other temperatures on request
Storage and transport temperature50°C .. +55°C
Relative humidity5% .. 95%, non condensing
AltitudeMax. 1000m above NN; at >1000m data required
Protection degree (secondary terminal)IP54

Application conditions

StandardIEC 61869-2 / IEEE C57.13; etc.
Rated short-time thermal current (Ith)100 x In/1s, max. 100kA/1s; other duration on request
Continuous thermal current (Icth)Up to 200%
Rated insulation level0,72/3/-kV
Rated frequency50/60Hz
Class of insulationE
GSKF 400