GSK 400

Split-Core Current Transformer

The GSK 400 are cast-resin insulated current transformers for indoor applications. They are suitable to put on cables or bus-bars.

Primary current:30 .. 10.000A
Secondary current:1A or 5A; other options available on request
Accuracy class:As required. For example 0,5, 5P20
GSK 400

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Relative humidity5% .. 95%, non condensing

Application conditions

StandardIEC 61869-2/IEEE C57.13, etc.
Rated short-time thermal current (Ith)100 x In/1s, max. 100kA/1s, other duration on request
RatedDynamicCurrentIdyn2,5 x Ith
Rated insulation level1,2/6/-kV
Rated frequency50/60Hz
Rated outputAs required. For example 10VA, 15VA
Secondary terminalScrew terminals M5 (max. 2,5Nm)
GSK 400

Downloads for GSK 400

1Downloads available