6G2073

Current Transformer Earth fault

The GSA 170 is a cast-resin insulated current transformer for indoor applications. They are suitable for cables or bus-bars. The GSA 170 Earth-fault is dedicated to measure phase displacement of a current. Both fixed core transformers (GSA) and split-core transformers are available (GST/GSK).

Rated primary current:60A
Rated secondary current:1A
Rated output:As required. For example 1,2VA
ø 1106G2073

General technical specifications

This product is designed to be safe under the following conditions:

Environmental conditions

LocationIndoor use
Ambient air temperature-5°C .. +40°C, other temperatures on request
Storage and transport temperature-25°C .. -50°C
Relative humidity5% .. 95%, non condensing
AltitudeMax. 1000m above NN; at >1000m data required
Protection degree (secondary terminal)IP20

Application conditions

StandardIEC 61869-2
Rated short-time thermal current (lth)20 kA / 1 s
RatedDynanimcCurentLdyn2,5 x Ith
Rated insulation level0,72/3/-kV
Rated frequency50/60Hz
Class of insulationE
Rated secondary current1A
Secondary terminalScrew terminals M5 (max. 2,5Nm)
Rated primary current60A
Accuracy class1,2VA - 1Fs10
6G2073

Downloads for 6G2073

1Downloads available
Aafje Heinhuis

Talk to sales

“We are the international manufacturer of measuring, revenue metering and protection transformers for energy generation, energy transport and distribution, energy accounting and energy management. Please contact me for the best solution for you.”

Aafje Heinhuis, Key Account Manager
6G2073

6G2073