UGE
Single Pole Voltage Transformer

UGE C1

The UGE C1 is used for measurement and protection in applications, especially in medium-voltage switchgears. The single pole indoor voltage transformer can be used up to 17,5kV

2/√3kV – 15,4/√3kV
100/√3V or 110/√3V, other options available on request
As required. For example 10, 15 or 30VA
Ask an offer now
jerry

"Our customers expect us to be able to offer them a solution for every challenge. For which challenge are you looking for a solution?"

Jerry van Zundert, Sales Manager
+31 (0)521 533 333
Order specifications
RatioWinding 1Winding 2RangeArticle number
10.000:√3 / 100:√3 / 100:30-20VA cl 0.260VA 3P12kV6U2011
11.000:√3 / 100:√3 / 100:30-20VA cl 0.260VA 3P12kV6U2012
11.000:√3 / 110:√3 / 110:30-20VA cl 0.260VA 3P12kV6U2110
10.000:√3 / 110:√3 / 110:30-20VA cl 0.260VA 3P12kV6U2112
11.000/13 // 110:13 // 110/3 V or 10.000/13 // 100:13 // 100/3 V 0-20VA cl 0.2 or 0-15VA cl 0.260VA 3P12kV6V2901
For the customized design of your ELEQ voltage transformer the following information is required:

Mandatory
Rated primary voltage
Rated secondary voltage
Rated output
Accuracy class
Frequency

Optional
Other relevant requirements
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-5°C .. +40°C, other temperatures on request
-25°C .. +50°C
5% .. 95%, non condensing
Max. 1000m above NN; at >1000m data required
IP20
Application conditions
IEC 61869-3/IEEE C57.13, etc.
500VA measuring winding in total 100VA residual winding
1,9 x Un for 8 h, 1,2 x Un continuous
17,5/38/95kV
50/60Hz
E
2/√3kV – 15,4/√3kV
100/√3V or 110/√3V, other options available on request
As required. For example 10, 15 or 30VA
As required. For example 0,2, 3P
M10 (20Nm)
Screw terminals M5 (max. 2,5Nm)
Downloads