Max Ø 50 mm
Cast-resin Current Transformer

SVA105-100-50

The SVA105 is especially designed for application in medium voltage installations around insulated cables.

100/5A .. 600/5A and 100/1A .. 600/1A
0,2S, 0,5S, 1, 5P10, 10P10
1,5-10VA
Ask an offer now
We never go for the simplest solution, but for the best solution, for you, as a customer. Please contact me for the best solution for you.
Wim van Turennout, Key Account Manager
+31 (0)6 2039 5494
Order specifications
Burden Model Ratio Class Article number
3-5VA SVA105-100-50 100/1A 0,5-1 4SV501
3-5VA SVA105-100-50 200/1A 0,5-1 4SV502
3-5VA SVA105-100-50 300/1A 0,5-1 4SV503
3-5VA SVA105-100-50 400/1A 0,5-1 4SV504
3-5VA SVA105-100-50 600/1A 0,5-1 4SV506
2,5VA SVA105-100-50 100/5A 0,2S 4SV521
2,5VA SVA105-100-50 200/5A 0,2S 4SV522
5VA SVA105-100-50 100/5A 0,5S 4SV531
7,5VA SVA105-100-50 200/5A 0,5S 4SV532
10VA SVA105-100-50 300/5A 0,5S 4SV533
10VA SVA105-100-50 400/5A 0,5S 4SV534
10VA SVA105-100-50 600/5A 0,5S 4SV536
4VA SVA105-100-50 150/1A 5P10 4SV550
4-7VA SVA105-100-50 100-200/1A 5P10 4SV551
4-7VA SVA105-100-50 200-400/1A 5P10 4SV552
4-7VA SVA105-100-50 300-600/1A 5P10 4SV553
4-7VA SVA105-100-50 400-600/1A 5P10 4SV554
1,5-3-6VA SVA105-100-50 50-100-200/1A 10P10 4SV590
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-10°C .. +55°C
5% .. 85%, non condensing
IP20
Application conditions
IEC 61869-2
20 kA3s
1
0,72/3/-kV
50/60Hz
E (120°C)
Max Ø 50 mm
Screw terminals Ø 5mm. Wire diameter max. 6mm² solid max 4mm² stranded
Downloads
The following downloads are available for this product.