SVA105
Cast-resin Current Transformer

SVA105-100-50

The SVA105 is especially designed for application in medium voltage installations around insulated cables.

100/5A .. 600/5A and 100/1A .. 600/1A
0,2S, 0,5S, 1, 5P10, 10P10
1,5-10VA
Ask an offer now
Foto-4

“We are the international manufacturer of measuring, revenue metering and protection transformers for energy generation, energy transport and distribution, energy accounting and energy management. Please contact me for the best solution for you.”

John den Ouden, Key Accountmanager
+31 (0) 521 533 318
Order specifications
ModelRatioBurdenClassArticle number
SVA105-100-50100/1A3-5VA0,5-14SV501
SVA105-100-50200/1A3-5VA0,5-14SV502
SVA105-100-50300/1A3-5VA0,5-14SV503
SVA105-100-50400/1A3-5VA0,5-14SV504
SVA105-100-50600/1A3-5VA0,5-14SV506
SVA105-100-50100/5A2,5VA0,2S4SV521
SVA105-100-50200/5A2,5VA0,2S4SV522
SVA105-100-50100/5A5VA0,5S4SV531
SVA105-100-50200/5A7,5VA0,5S4SV532
SVA105-100-50300/5A10VA0,5S4SV533
SVA105-100-50400/5A10VA0,5S4SV534
SVA105-100-50600/5A10VA0,2S4SV536
SVA105-100-50150/1A4VA5P104SV550
SVA105-100-50100-200/1A4-7VA5P104SV551
SVA105-100-50200-400/1A4-7VA5P104SV552
SVA105-100-50300-600/1A4-7VA5P104SV553
SVA105-100-50400-600/1A4-7VA5P104SV554
SVA105-100-5050-100-200/1A1,5-3-6VA10P104SV590
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-10°C .. +55°C
5% .. 85%, non condensing
IP20
Application conditions
IEC 61869-2
20 kA3s
1
0,72/3/-kV
50/60Hz
E (120°C)
Max Ø 50 mm
Screw terminals Ø 5mm. Wire diameter max. 6mm² solid max 4mm² stranded
Downloads
The following downloads are available for this product.