Generator Current Transformer
IGWR D25
The IGWR D25 is used for measurement and protection in applications with vibration requirements like power generators. The cast resin insulated indoor supporting-type current transformer can be used up to 17,5kV.
5-1500A
1A or 5A, other options available on request
As required. For example 2,5, 10 or 30VA

"We never go for the simplest solution, but for the best solution, for you, as a customer. Please contact me for the best solution for you."
Wim van Turennout, Key Account Manager
+31 (0)521 533 313
Order specifications
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-25°C .. +80°C, other temperatures on request
-50°C .. +80°C
5% .. 95%, non condensing
Max. 1000m above NN; at >1000m data required
IP20
Application conditions
IEC 61869-2 / IEEE C57.13, etc.
2,5 x Ith, max. 125kA
Up to 200%
17,5/38/95kV
50/60Hz
E
As required. For example 0,2S, 5P10
M12 (40Nm)
Screw terminals M5 (max. 2,5Nm)