Supporting Type Current Transformer
IGW C1
The IGW C1 is used for measurement and protection in applications. The cast resin insulated indoor supporting-type current transformer can be used up to 17,5kV.
5 .. 1500A
1A or 5A, other options available on request
As required. For example 0,2S, 5P10

"Our customers expect us to be able to offer them a solution for every challenge. For which challenge are you looking for a solution?"
Jerry van Zundert, Sales Manager
+31 (0) 521 533 333
Order specifications
Range | Ratio | Burden | Class | Ith | Article number |
---|---|---|---|---|---|
12kV | 50-100-150/5A | 1-10VA | 0,2S | 2x20kA/ 1S | 612061 |
12kV | 2X25/5A | 0,5-10VA | 0,2S FS5 | 2x10kA/ 1S | 612540 |
12kV | 2X50/5A | 0,5-10VA | 0,2S FS5 | 2x20kA/ 1S | 612560 |
12kV | 2X100/5A | 0,5-10VA | 0,2S FS5 | 2x20kA/ 1S | 612600 |
12kV | 2X150/5A | 0,5-10VA | 0,2S FS5 | 2x20kA/ 1S | 612620 |
12kV | 2X200/5A | 0,5-10VA | 0,2S | 2x20kA/ 1S | 612640 |
General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-5°C .. +40°C, other temperatures on request
5% .. 95%, non condensing
Application conditions
IEC 61869-2/IEEE C57.13, etc.
100 x In/1s, max. 50kA/1s
2,5 x Ith, max. 125kA/1s
17,5/38/95kV
50/60Hz
M12 (40Nm)
Screw terminals M5 (max. 2,5Nm)
As required. For example 2,5, 10 or 30VA